What is the requirement for Heat Balance?

Turning energy savings into profits!

What is the requirement for Heat Balance?

The verification of chilled water plant instrument using the heat balance –substantiating test shall be in accordance to AHRI 550/590. The heat balance shall be conducted over the entire normal operating hours with more than 80% of the computed heat balance within ±5% over the audit period (1 week).

Formula_1

The computation formula is as follows:

For open drive chillers, the Winput shall take into account the motor efficiency provided by the manufacturer. An example is provided as follows:

Input power (measured) = 100kW
Motor rated efficiency (η) = 90%
Adjusted Winput = 100kW x90%
                               = 90kW

In the event where hydraulic losses of pumps constitute a substantial heat gain, these losses have to be properly accounted for. The value shall be determined from pump efficiency values provided by the manufacturer. An example is as follows:

Motor input power (measured) = 30kW (A)
Motor rated efficiency (η) = 90% (B)
Pump rated efficiency (η) = 80% (C)
Hydraulic losses = (A) x (B) x (100%- (C) )
                                              = 30kW x90% x(100%-80%)
                                              = 5.4kW
Adjusted Winput = kWi(chillers) + 5.4kW

To Top